Fire Resistant Glass

Features

Double Layers Fire Resistant Glass

Features

Job Reference of Double Layers Intumescent Fire Resistant Glass
  • Class A Fireproof Glass
  • Insulated or also known as Laminated Configuration
  • Filled with Extraordinary Fire Proof Gel between Two Glass Panes
  • Absolutely Free of Bubbles
  • High Transparency
  • High Impact Strength
  • Extraordinary Fire Proof Integrity
  • Block Smoke
  • Excellent Weather Proof
  • Glass Fulfilling Chinese or British BS476 Standards
Job Reference of Double Layers Intumescent Fire Resistant Glass Job Reference of Double Layers Intumescent Fire Resistant Glass Job Reference of Double Layers Intumescent Fire Resistant Glass

Specifications

Fulfill Chinese GB15763.1 - 2001 Standard

Glass Thickness Class Fire Resist Duration Weight Fire Side Temperature Average Max. Non Fire Side Temperature Acoustic Insulation
45 ± 2 mm Supreme (3 hrs) 180 Min. ~ 52 kg / m2 1113 ℃ ≤ 129 ℃ ~ 60 dB
32 ± 2 mm Class A / Grade I 90 Min. ~ 52 kg / m2 1060 ℃ ≤ 140 ℃ ~ 60 dB
26 ± 2 mm Class A / Grade II 72 Min. ~ 45 kg / m2 1017 ℃ ≤ 120 ℃ ~ 55 dB
23 ± 2 mm Class A / Grade III 54 Min. ~ 40 kg / m2 1000 ℃ ≤ 140 ℃ ~ 45 dB
19 ± 2 mm Class A / Grade III 45 Min. ~ 35 kg / m2 939 ℃ ≤ 100 ℃ ~ 35 dB
15 ± 2 mm Class A / Grade IV 30 Min ~ 30 kg / m2 900 ℃ ≤ 100 ℃ ~ 35 dB

Fulfill British BS476 Part 22 - 1987 Standard

Models Glass Thickness Series Weight Fire Side Temperature Average Max. Non Fire Side Temperature
Integrity Insulation
EI 120 42 ± 2 mm 120 Min. 120 Min ~ 65 kg / m2 1100 ℃ ≤ 68 ℃
EI 60 25 ± 1.5 mm 60 Min. 60 Min. ~ 45 kg / m2 980 ℃ ≤ 60.5 ℃
EI 30 19 ± 1.3 mm 30 Min. 30 Min. ~ 35 kg / m2 950 ℃ ≤ 74.6 ℃